A customer messages you on WhatsApp: "I want a 5kW inverter for my house. How many batteries?" If you answer "two" or "four" without asking anything else, you are guessing — and the customer will find out when his lights die at 9 PM.
Here is the calculation we use, with real numbers from our 5kVA/48V inverter (model WS-5048) and a 48V 200Ah lithium battery (S48200).
Step 1: Decide what the inverter will actually carry
A 5kVA inverter does not mean the house uses 5kW all night. A typical African household load at night looks like this:
| Load | Power | Hours used at night |
|---|---|---|
| LED lights (10 points) | 100W | 5h |
| TV + decoder | 120W | 4h |
| 2 fans | 140W | 6h |
| Fridge (cyclic) | 150W avg | 8h |
| Phone/laptop charging | 60W | 3h |
| Water pump (occasional) | 750W | 0.5h |
Total energy per night ≈ 3.2 kWh. The peak demand (fridge compressor start + pump together) is what decides the inverter size — that is why 5kVA, not the daily energy.
Step 2: Convert energy to battery capacity
For a 48V system:
Capacity (Ah) = Daily energy (Wh) ÷ System voltage (V) ÷ Depth of discharge
With lithium (80% DoD, per the S48200 spec sheet): 3,200Wh ÷ 48V ÷ 0.8 ≈ 83Ah. One 48V 100Ah battery (4.8kWh, our S48100) covers one night with margin.
With tubular lead-acid (50% DoD is the honest number): 3,200Wh ÷ 48V ÷ 0.5 ≈ 133Ah. One 48V 150Ah+ bank, or two 12V 200Ah units in series.
Step 3: Ask how many nights of autonomy
This is where the real answer lives. One battery = backup for grid failure tonight. Two batteries in parallel = you survive a cloudy day if you have solar panels. Three = you stop thinking about it.
Our rule of thumb for installers quoting residential jobs:
- 1 × 48V100Ah lithium — minimum viable, grid-tied mindset
- 2 × 48V100Ah (or 1 × 200Ah) — comfortable for a home with 2–3kWp of panels
- 3+ parallel — shops, clinics, or homes running AC units at night
The S48-series supports up to 15 units in parallel, so starting with one and expanding later is technically fine — but tell the customer the BMS and cabling should be planned for expansion from day one.
The three mistakes that kill systems
1. Sizing batteries from inverter wattage instead of load. A 5kVA inverter with one 100Ah battery works — until the owner tries to run everything at once and the low-voltage protection cuts the house off at midnight. Match the battery to the load profile, not the inverter badge.
2. Ignoring charging current. Our WS-5048 charges at up to 30A AC. At 48V, that is roughly 1.4kW of charging power. If the nightly consumption is 3.2kWh, the grid needs ~2.5 hours to refill the battery — fine. But if the customer expects solar to refill a 10kWh bank daily, the PV array must actually deliver that, which leads to mistake 3.
3. Overestimating PV input on low-frequency inverters. This inverter family accepts a maximum PV open-circuit voltage of 150V DC (the 10–15kVA models accept 250V). You cannot hang 10 panels in one series string the way you would on a 450V high-frequency hybrid. Panel strings must be built in series-parallel within that window — we cover this in detail in our article on PV input voltage.
What we tell customers
Send us your load list (what runs at night, for how long) and we will return a sizing sheet: inverter model, battery bank, panel configuration, and expected backup time — free, before you pay anything. Installers in Nigeria, Ghana and francophone West Africa use this to quote their own jobs in under an hour.
Questions on a specific project? Message us on WhatsApp — a real engineer answers, not a chatbot.